Actuator Selection Process
Sizing Information
Choosing the correct actuator is as important as selecting the correct valve.
The information offered below is presented in an effort to assist in the choice
of the proper actuator for your application.
If you are unsure of your selection and feel you need assistance,
do not hesitate to contact your local FLO-TORK representative or the
FLO-TORK Corporate office.
Prior to beginning the actuator selection process it is necessary that you
have the following information:
- The maximum torque required to break (unseat) the valve element from its
fully closed (seated) position, against the maximum pressure differential.
- The maximum running torque required to operate the valve against the
applicable flow rate and the differential pressure in the valve.
- The maximum torque required to seat the valve in its fully open position
- (applicable for ball & plug valves).
- The maximum torque required to unseat the valve from its fully open position
to start closing (applicable for ball & plug valves).
- The maximum torque required to close (seat) the valve in its fully closed position.
- The direction of operation required to close the valve -
clockwise or counterclockwise. Normal assembly of the SERIES M scotch-yoke actuator
is clockwise to close. NOTE: This is important as the SERIES M actuator is designed
with a 5 degree torque plug cant that provides different output capacities at
each end of stroke.
NOTE: Determine if the torque values provided include a sufficient safety factor
for the application.
In addition to the torque data described above, the following application
information is required to begin the selection process.
- What is the supply media to the actuator?
- Pneumatic
- Hydraulic -
What type of hydraulic fluid is to be used?
- What are the minimum/maximum operating media supply pressures?
- Will the actuator be double acting or spring return?
- If a spring return stroke is required, is it fail open or fail close?
These guidelines are provided to assist in choosing the proper SERIES M
scotch-yoke actuator using the data discussed above.
The ACTUATOR SELECTION PROCESS listed below assumes a
CLOCKWISE ROTATION TO CLOSE
the valve and that the maximum torque requirement is to break (unseat)
the valve element from its fully closed position.
If these assumptions are incorrect, an alternate selection process must be used.
Actuator Selection Process
Double Acting Actuators
NOTE: FLO-TORK's SERIES M double acting torque charts are based on a
clockwise rotation to close the valve.
The torque charts provide start (break) torque values shown at 01,
run torque values shown as minimum (min) and end (fully open) torque values shown at 900.
Be sure that the maximum valve torque values at all positions of rotation are
less than the minimum actuator output torque values.
- From the actuator torque charts select the pressure column that is equal to or
less than the minimum operating pressure available.
- Move down the selected pressure column until you find a torque output that
is equal to or exceeds the maximum break (unseating), run (dynamic) and fully
open torque values of the valve.
- Move to the left in that line and determine the SERIES M
model number in the model column.
- Now that the actuator has been selected, use the torque charts
to verify that the maximum operating pressure does not exceed the maximum pressure
rating of the actuator and that the output torque of the actuator does not
exceed the allowable torque rating for the valve stem at the maximum operating pressure.
If either of these ratings are exceeded then the maximum operating
pressure must be reduced (i.e. adding a pressure regulating valve)
or an alternate actuator must be selected.
Spring Return Fail Close (CW) Actuators
NOTE: The SERIES M spring return torque charts are based on a clockwise
spring stroke and provide the start (break), run (minimum) and end (closing)
torque outputs for the spring stroke in addition to the pressure stroke output
torques for the same positions of rotation.
The spring break torque (highest spring output torque) is shown at the 901 position.
This corresponds with the lowest pressure stroke output torque which is
also at the 901 position.
NOTE: The actuator output torque must exceed the maximum torque requirements
of the valve at all positions for both the spring and the pressure strokes.
- Start with the spring torque column and select a spring end torque at 01 that equals
or exceeds the maximum closing (seating) torque required for the valve.
- Move to the left in that spring line to a pressure column that is equal to or less
than the minimum operating pressure. The pressure stroke column start (break) torque
(shown at 0") must equal or exceed the maximum break torque. The pressure end torque
(shown at 900) must exceed the valve torque requirement at the full open or full
flow position. The pressure stroke is counterclockwise rotation.
- If the pressure stroke output torque value does not exceed the maximum required
at each position (00 , MIN, 900) then it will be necessary to select a larger model
that meets or exceeds the torque requirements in both the spring and pressure columns.
- Now that the actuator has been selected, use the pressure torque charts to determine
that the maximum operating pressure does not exceed the maximum pressure rating of the
actuator and the torque Output does not exceed the allowable torque for the valve stem
at the maximum operating pressure. If either of these ratings are exceeded, the maximum
operating pressure must be reduced (i.e. adding a pressure regulating valve) or an
alternate actuator must be selected.
- At the time of order placement, it is most important to confirm/specify the
direction of the spring stroke. Clockwise rotation to close is standard.
Spring Return Fail Close (CCW) Actuators
NOTE: For fail open actuators that require a counterclockwise stroke,
the spring cylinder is assembled on the opposite side of the housing and
the torque plug is reversed; therefore, the output torque values shown in
the torque charts are unchanged but the values at the 01 and 901 positions will be reversed.
- Starting with the spring torque column, select a spring that has break
torque (901), minimum torque (MIN) and end torque (00) values that exceed
the maximum valve torque requirements.
- Move to the left in that spring line to a pressure column that is equal to or
less than the minimum operating pressure. Verify that the minimum output torque and
the output torque at the 901 position (seat torque) exceed the valve torque requirements.
- If the pressure stroke output torque values do not exceed the maximum valve
torque requirements at each of the three positions then you must select a larger
model that meets or exceeds the torque required in both the spring and pressure columns.
- Now that the actuator has been selected, use the pressure torque chart to
determine that the maximum operating pressure does not exceed the maximum pressure
rating of the actuator and the torque output does not exceed the allowable torque
for the valve stem at the maximum operating pressure. If either of these ratings
are exceeded, the maximum operating pressure must be reduced (i.e. adding a pressure
regulating valve) or an alternate actuator must be selected.
- At the time of order placement, it is most important to confirm/specify the
direction of the spring stroke. Clockwise rotation to close is standard.
Dimensions
Included in the SERIES M literature are outline dimensions for both double
acting and spring return models. Please refer to these catalog pages to determine
the physical size of the actuator selected.
NOTE: The values shown on the torque charts are minimum output based on
ideal conditions. The actual torque output may vary based on adjustor stop screw
position, alignment, service time between lubrication, and other influencing factors.